Guides
Voltage-drop in the transformer as a function of load
The table shows the secondary voltage (V) at no-load, at 50%
load and at 100% load at 230 V primary voltage
| Transformer power VA |
No-load |
50% load |
100% load |
| 24 |
13,1 |
12,2 |
11,6 |
| 40 |
12,8 |
12,2 |
11,6 |
| 60 |
12,3 |
11,9 |
11,6 |
| 150 |
12,0 |
11,8 |
11,6 |
| 210 |
12,0 |
11,7 |
11,6 |
| 250 |
12,0 |
11,7 |
11,6 |
| 300 |
12,0 |
11,7 |
11,6 |
| 480 |
11,9 |
11,7 |
11,6 |
|