Guides
Resistance table
The table shows the resistance measured in milliohms for 2-wire leads at the
indicated length of the cable.
Wire- area (mm2) |
1 m |
2 m |
3 m |
4 m |
5 m |
6 m |
7 m |
8 m |
9 m |
10 m |
| 2x0,75 |
54 |
108 |
162 |
216 |
270 |
324 |
378 |
432 |
486 |
540 |
| 2x1,0 |
40 |
80 |
120 |
160 |
200 |
240 |
280 |
320 |
360 |
400 |
| 2x1,5 |
28 |
56 |
84 |
112 |
140 |
168 |
196 |
224 |
252 |
280 |
| 2x2,5 |
16,4 |
32,8 |
49,2 |
65,6 |
82,0 |
98,4 |
115 |
131 |
147 |
164 |
| 2x4,0 |
10,2 |
20,4 |
30,6 |
40,8 |
51,0 |
61,2 |
71,4 |
81,6 |
91,8 |
102 |
| 2x6,0 |
6,8 |
13,6 |
20,4 |
27,2 |
34,0 |
40,8 |
47,6 |
54,4 |
61,2 |
68 |
|